Valve testing system VPS 504 for multiple actuators Valve proving system for automatic shutoff valves as per EN 161, Class A and Class B The VPS 504 may be used with any other valve whose tightness in counter-flow direction excludes by construction a leakage in flow direction. The VPS 504 is suitable for all DUNGS valves according to EN 161 Classes A and B. The VPS 504 is the valve proving system for DUNGS multiple actuators. The valve proving system complies with EN 1643: - Equipment operates independent of residual pressure in the range of the permissible operating range. - Test volume ≤ 4 l - Setting work not necessary on site - Short test period: ≈ 10 s, max. 36 s - Tightness or leaks are displayed by an LED - External fault display possible for series 02, series 04 and S05 - Group fault alarm optional for S01 (SSM) - Suitable for TRD systems - Electrical connection possible by plug connection S01, 02, 03. No rewiring is required for contact allocation as per DIN 4791. - S04 and S05: electrical connection at screw terminals via PG 13.5 cable entry